10. Peripheral devices
When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious injury.
Mandatory
action
Connect grounding cables securely.
Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric
leak.
Be Grounded
10.1 Selection of wiring materials and devices
Selection of cable size
Voltage class
1 phase
240V class
3 phase
500V class
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 (Single-phase models are R/L1
and S/L2/N) and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed
30m. If there is a need to bring the inverter into UL compliance, use wires specified in chapter 9.
Note 2: For the control circuit, use shielded wires 0.75 mm
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The cable sizes specified in the above table apply to HIV cables (copper cables shielded with an insulator
with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.
Note 5: In case of aul=2 setting, be sure to use the cable size of power circuit for 1 rating up motor.
Power circuit
Applicable
(Note 1, 5)
motor (kW)
For Japan
IEC
(JEAC800
compliant
1-2005)
0.2
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
2.5
2.0
2.2
4.0
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
4.0
2.5
2.0
5.5
4.0
2.0
7.5
6.0
3.5
11
10.0
5.5
15
16.0
8.0
18.5
16.0
8.0
Warning
2
Cable size (mm
) (Note 4)
Braking resistor
(optional)
For Japan
IEC
(JEAC800
compliant
compliant
1-2005)
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
2.5
2.0
4.0
2.0
6.0
3.5
-
-
2
or more in diameter.
J-1
E6581697
Grounding earth cable
For Japan
IEC
(JEAC800
1-2005)
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
6.0
3.5
10.0
5.5
16.0
5.5
-
-
10