10. Peripheral devices

 When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious injury.
Mandatory
action
 Connect grounding cables securely.
Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric
leak.
Be Grounded

10.1 Selection of wiring materials and devices

 Selection of cable size
Voltage class
1 phase
240V class
3 phase
500V class
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 (Single-phase models are R/L1
and S/L2/N) and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed
30m. If there is a need to bring the inverter into UL compliance, use wires specified in chapter 9.
Note 2: For the control circuit, use shielded wires 0.75 mm
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The cable sizes specified in the above table apply to HIV cables (copper cables shielded with an insulator
with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.
Note 5: In case of aul=2 setting, be sure to use the cable size of power circuit for 1 rating up motor.
Power circuit
Applicable
(Note 1, 5)
motor (kW)
For Japan
IEC
(JEAC800
compliant
1-2005)
0.2
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
2.5
2.0
2.2
4.0
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
4.0
2.5
2.0
5.5
4.0
2.0
7.5
6.0
3.5
11
10.0
5.5
15
16.0
8.0
18.5
16.0
8.0
Warning
2
Cable size (mm
) (Note 4)
Braking resistor
(optional)
For Japan
IEC
(JEAC800
compliant
compliant
1-2005)
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
2.5
2.0
4.0
2.0
6.0
3.5
-
-
2
or more in diameter.
J-1
E6581697
Grounding earth cable
For Japan
IEC
(JEAC800
1-2005)
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
6.0
3.5
10.0
5.5
16.0
5.5
-
-
10