Applicable parameters: Command mode selection cmOd
There are two starting and stopping methods as shown below. Select either method.
Starting and
stopping method
Terminal Block
RUN / STOP
keys
Applicable parameters: Frequency setting mode selection fmOd
There are three methods of setting the frequency. Select a suitable method.
Frequency
setting method
Terminal block
0-10V, 4-20mA
External potentiometer
UP / DOWN
keys
Built-in potentiometer
Use the parameter F200 to specify the order of priority of two frequency commands to be input to
the terminal block.
Settings of frequency
priority parameter F200
0
1
TOSHIBA
Selecting the Starting and Stopping Method
Set value
0
The motor starts when the F (forward) or R (reverse) terminal on
the terminal block is connected to CC. Acceleration and
deceleration is performed at the programmed rate shown in the
Basic Parameters on page 36.
1
When the RUN key on the panel is pressed, the motor is
accelerated according to the acceleration pattern. When the
STOP key is pressed, the motor is decelerated according to the
deceleration pattern.

Setting the Frequency Command Method

Set value
0
A frequency setting input to VIA, VIB or II on the terminal block is
used.
1
The frequency set with the 'up' or 'down' key on the panel is used.
The UP/DOWN key lamp is on when this function is enabled.
2
The value set with the built-in potentiometer is used. The built-in
potentiometer lamp is on when this function is enabled.
Prior
terminals
VIA or II
If 0 is input to the VIB terminal, a command input to the VIA or II
terminal is valid.
VIB
If 0 is input to the VIA and II terminals, a command input to the VIB
terminal is valid.
32
cmOd
Description
fmOd
Description
Description