6.17.10 Cumulative operation time alarm setting
: Cumulative operation time alarm setting
• Function
*
■ Setting of output signal l
6
6.17.11 Over-voltage stall protection level
: Over-voltage stall protection level
⇒ For more details, see section 6.12.4.
This parameter allows you to set the inverter so that it will put out an alarm signal after a lapse of the
cumulative operation time set with .
"0.1" displayed on the monitor refers to 10 hours, and therefore "1" denotes 100 hours.
Ex.: 38.5 displayed on the monitor = 3850 (hours)
Title
Function
Cumulative operation time
alarm setting
Ex.: When assigning the cumulative operation alarm signal output function to the RY-RC terminals
Title
Function
Output terminal selection 1A
(RY-RC)
Adjustment range
0.0-999.9
Adjustment range
0-255
F-66
E6581381
Default setting
610.0
Setting value
42 (negative
logic 43)