Appendix 4
Output terminal function selection parameters
Table 8-5 is the function setting of 3 output terminals.
Table 8-6 is the output terminal functions.
Table 8-5 Output terminal function selection parameters
Communication
Title
No.
f130
0130
f131
0131
f132
0132
f137
0137
f138
0138
Note 1: For an explanation of the adjustment range, see Table 8-6 "Output terminal functions."
Table 8-6 Output terminal functions
Select the positive-logic of the output terminal functions for the My function-S.
Note that negative-logic settings cannot be used for the output terminals.
Input
Parameter
setting
setting
Frequency lower limit
Frequency upper limit
Low-speed detection
signal
Output frequency
attainment signal
(acceleration/decelerat
ion completed)
Set frequency
attainment signal
Fault signal
(trip output)
Over-current detection
pre-alarm
Overload detection
pre-alarm
Overheat detection
pre-alarm
Overvoltage detection
pre-alarm
Power circuit
undervoltage detection
Small current
detection
Over-torque detection
Function
Output terminal selection 1A (RY-RC)
Output terminal selection 2A (OUT)
Output terminal selection 3 (FL)
Output terminal selection 1B (RY-RC)
Output terminal selection 2B (OUT)
Function
ON: Output frequency is more than ll
OFF: ll or less
ON: Output frequency is ul or more
OFF: less than ul
ON: Output frequency is f100 or more
OFF: less than f100
ON: Output frequency is within command frequency ± f102
OFF: more than command frequency ± f102
ON: Output frequency is within f101± f102
OFF: more than f101± f102
ON: Inverter tripped
OFF: Inverter not tripped
ON: Output current is f601 or more
OFF: less than f601
ON: f657(%) or more of calculated value of overload protection level
OFF: Less than f657(%)
ON: Approx. 95C or more of IGBT element
OFF: Less than approx. 95C (90C or less after detection is turned on)
ON: Overvoltage limit in operation
ON: Power circuit undervoltage (
OFF: Undervoltage detection canceled
ON: After output current comes to f611 or less, value of less than
f611 + f609 for f612 set time
OFF: more than f611
(f611 + f609 or more after detection turns on)
ON: After torque comes to f616 or more, value of more than
f616 – f619 for f618 set time
OFF: less than f616
(f616 – f619 or less after detection turns on)
Operation output specifications (in case of positive logic)
moff
- 31 -
E6581865
Adjustment range
Default setting
(Note 1)
-
-
-
-
-
255
) detected
4
6
10