[D.C. braking under normal conditions]
(Forward/reverse DC braking priority control
Output frequency [Hz]
Set frequency
Reference frequency
0
Operating signal (F-CC)
If and > reference frequency
If > reference frequency >
If and > reference frequency
If an operation command is entered during D.C. braking : D.C. braking is discontinued to restart the
[Priority to DC injection braking during forward/reverse operation]
(Forward/reverse run D.C. braking priority control = (ON))
Output frequency [Hz]
Set frequency
Reference frequency
signal (F-CC)
signal (R-CC)
During normal forward/reverse run( )
Not recognized as a stop command, so that DC injection braking is not active.
If a reverse run (or forward) command is entered during forward run (or reverse)
( ) DC injection braking starts when the frequency set with exceeds the
reference frequency during deceleration.
If an operation command is entered during D.C. braking priority is given to D.C. braking.
6.8.2 Motor shaft fixing control
Function
This function is useful for preventing the motor shaft from rotating freely or for
preheating the motor.
Motor shaft fixing control
F-16
=[OFF])
: DC injection braking
: Operation at command frequencies,
: DC injection braking
operation.
: DC injection braking
time [ ]
ON
OFF
: DC injection braking
time [ ]
ON
OFF
ON
OFF