Commissioning
8.3 Commissioning using the AOP30 operator panel
If an optimization run is not carried out, the motor control uses the motor characteristic
values calculated from the rating plate data rather than the measured values.
During optimization runs, the drive initiates motor movements that can reach the maximum
motor speed. The EMERGENCY OFF functions must be fully operational during
commissioning. To protect man and machines, the relevant safety regulations must be
observed.
8.3.2

Status after commissioning

LOCAL mode (control via operator panel)
● You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
● Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
● You can set the setpoint using the "Increase" and "Decrease" keys or by entering the
8.3.3

Resetting parameters to factory settings

The factory settings represent the defined original status of the unit on delivery.
Resetting the parameters to the factory settings means that all the parameter settings made
since the system was delivered are reset.
Setting the parameter filter to "Parameter reset"
<MENU> <Commissioning/Service> <OK> <Device commissioning> <OK> <30: Parameter
Reset> <OK>
Restoring all parameters to their factory settings
All of the unit parameters are reset to their factory settings. The AOP30 is powered down
and back up again during this process.
236
DANGER
appropriate numbers on the operation screen using the numeric keypad.
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
SINAMICS DCM DC Converter