Shut down DEFINITY AUDIX system [from
R5/R6/R7/R8si]
Return to Task List
A yellow caution sticker on the system's power unit notifies you to shut down the AUDIX before
powering down the system.
!
Neglecting to shut down an AUDIX assembly before powering down the system cabinet
where it resides can damage the AUDIX disk.
1
Log into the AUDIX as craft.
NOTE:
If you have a dadmin login and password, you can use them instead of craft and the craft
password.
2
Type
reset system shutdown
3
Press Enter again to start the shutdown.
The
SHUTDOWN Completed
takes about 2 minutes.
CAUTION:
If leaving AUDIX System in the carrier, back it out about 2 in. (5 cm) to eliminate the
possibility of damage due to power surges.
Return to Task List

Power down cabinet(s) [from R5/R6/R7/R8si]

Return to Task List
NOTE:
Before powering down the cabinet(s), make sure you have all replacement circuit packs
and new ATA flashcards nearby to minimize down time.
CAUTION:
Important system data such as BCMS data, records of queued ACD calls, Automatic
Wakeup requests, and Do Not Disturb requests will be lost on power down. You cannot
store to or retrieve data from tape or flash.
CAUTION:
On a DC-powered SCC, do not power down by reseating the power supply as it will trip
the breakers on the DC power cabinet.
SI Installation and Upgrades
June 2004
WARNING:
and press Enter.
message displays when the AUDIX is successfully shutdown. This
R5/R6/R7/R8si to Avaya Communication Manager
Task List: R5/R6/R7/R8si to Avaya Communication Manager