3
Connect the supplied cabinet AC power cord to the AC receptacle on the rear of the control
cabinet. Plug the opposite end of the cord into the dedicated electrical outlet.
Figure 6: Typical AC power and ground layout
1
2
3
4
7
Figure notes
1
Control cabinet
2
Circuit-breaker receptacle
3
Single-point ground block
4
8-ft power cord (2.5 m)
Return to Task List
Power up [from G3V4vs/R5vs/R6vs]
Return to Task List
Set the circuit breaker to ON.
CAUTION:
It may be necessary to reseat circuit packs. To prevent damage from static electricity,
always wear an Electromagnetic Compatibility (EMC) wrist strap (Comcode 900698226)
when handling all system components.
SI Installation and Upgrades
June 2004
G3V4vs/R5vs/R6vs to Avaya Communication Manager
Task List: DEFINITY vs to Avaya Communication Manager
On
On
Off
Off
5
8
6
5
NEMA 5-15 or 5-20 receptacle or equivalent
6
6 AWG (16-mm
approved ground
7
10 AWG (6-mm
r781851b CJL 030896
2
) CABINET GROUND wire to
2
) wire to CBC
159