Figure 143: Cable Routing to Bottom Terminal Blocks
Figure notes
1
Main Distribution Frame
2
AC Power Cord (AC-Powered
Cabinets Only)
3
Cable Slack Manager Number 1
4
Trunk/Auxiliary Field
5
Station Distribution Field
Coupled Bonding Conductor
The Coupled Bonding Conductor (CBC) connects to the single-point ground block and runs adjacent to
pairs in an associated telecommunications cable. The mutual coupling between the bonding conductor
and the pairs reduces potential differences in terminating equipment.
The conductor consists of a 10 AWG (#25) (2.5 mm
terminated at the CBC terminal bar at the Main Distribution Frame (MDF). A minimum of 12 inches
(30.48 cm) spacing must be maintained between the CBC and other power and ground leads.
The 10 AWG (#25) (2.5 mm
rear of the system cabinets, follow these cables to the MDF, and to terminate at the CBC.
SI Installation and Upgrades
June 2004
6
7
8
9
10
2
) wire tie-wrapped to the inside wiring cable and
2
) wire must be long enough to reach the telecommunications cables at the
Install Telecommunications Cabling
Coupled Bonding Conductor
r758432b MMR 052996
Cable Slack Manager Number 2
Cable Slack Manager Number 3
System Cabinet(s)
Building Cables (Through Cable
Trough)
2
10 AWG (#25) (6 mm
) Wire to
Coupled Bonding Conductor
415