Restore The Factory Settings (Without Safety Functions) - Siemens Sinamics G110M Operating Instructions Manual

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

5. Set p0971 = 1.
6. Wait until the inverter sets p0971 = 0.
7. Switch off the inverter supply voltage.
8. Wait until all LEDs on the inverter go dark.
9. Switch on the inverter supply voltage again.
You have restored the safety function settings of your inverter to the factory settings.
5.5.2

Restore the factory settings (without safety functions)

Restore the factory inverter settings
Procedure with STARTER
Proceed as follows to reset the inverter to factory settings:
1. Select your drive.
2. Go online.
3. Open "Drive Navigator".
4. Select the "Commissioning" button.
5. Press the "Factory setting" button.
6. ☑ In the screen form, select "After loading copy RAM to ROM".
7. Start the reset.
8. Wait until the inverter has been reset to the factory setting.
You have reset the inverter to factory settings.
Procedure with Startdrive
Proceed as follows to reset the inverter to factory settings:
1. Go online.
2. Select "Commissioning".
3. Select "Backing up/reset".
4. Select "All parameters are reset".
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Commissioning
5.5 Restoring the factory settings
137