Wall-Mounting (Style-5054); Floor-Mounting (Style-5054); Rack-Mounting (Style-5054); Floor-Mounting (Style-5070) - HindlePower ATevo Series Operations

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
between the mounting legs.
3.5.
3.5. Mounting ATevo
Mounting ATevo
Mount the ATevo so you can easily access the front panel AC Input (CB1) and DC Output (CB2)
Circuit Breakers. Choose from the following mounting methods:
1.
Wall-Mounting – Style-5054
2.
Floor-Mounting – Style 5054
3.
Rack-Mounting – Style 5054
4.
Floor-Mounting – Style 5070
3.5.1.

3.5.1. Wall-Mounting (Style-5054)

Wall-Mounting (Style-5054)
Wall-mounting is the standard method of installing the Style-5054 enclosure. When wall-
mounting ATevo, consider the following:
1. Refer to Style-5054 enclosure outline drawing":https://www.hindlepowerinc.com/media/
8d84537135b2cb1/je5251-00.pdf
2. Wall must be strong enough to properly support ATevo's weight, plus a safety factor. Refer
to Weight Table in
depending on the features, options, and accessories ordered with the unit.
3. Select conduit entrances with planned AC input and DC output wiring in mind. By using
pre-fab knockouts on enclosure sides or bottom, the enclosure shroud can be removed for
internal servicing without removing ATevo from the wall.
4. Location requirements:
a. Free of drips and splatter. If falling particles and liquids are a problem, install a
NEMA Type-2 drip shield accessory.
b. Between 0 and 122 °F / -18 and 50 °C, with relative humidity between 0% and 95%
non-condensing.
c. Must be free of flammable or explosive materials.
d. Maintain at least 6in / 152mm of free air on all vented surfaces for cooling.
e. Allow at least 36in / 914mm front clearance for operation and maintenance.
PROCEDURE
PROCEDURE
Install four (4) 0.25in / 6.4mm anchor bolts (not supplied) rated to support ATevo's weight plus
a minimum safety factor of two (2) times, into the wall. Place ATevo onto anchor bolts, add
appropriate mounting hardware, and tighten securely. Refer to the following graphics for
ATevo's wall-mounting pattern and specification.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Section 3.4, Moving
ATevo. The weight of your ATevo may be different,
Last modified: 11 May 2021
Last modified: 11 May 2021
Page 16 of 171