HindlePower ATevo Series Operations page 133

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
5. Connect wiring (#22-14 AWG) to appropriate terminals on the Auxiliary I/O Board
(A4-TB1).
6. Strip each wire 0.25in / 6.4mm, and tighten terminal screws.
7. Replace the safety shield.
8. Re-energize ATevo.
Notes
Notes
• Binary Inputs are configurable for 12Vdc, 24Vdc, 48Vdc, or 130Vdc.
• Terminal block (A4-TB1) is compression type, accepting #22-14 AWG wire.
• Correct polarization is required.
14.2.3.
14.2.3. Wiring Analog Input Connections
Wiring Analog Input Connections
Connections to the Analog Inputs are made through 5-pos
terminal block (A4-TB3). The terminal block is removable to
simplify wiring. Terminal connections are labeled along the
edge of the Auxiliary I/O Board next to terminal block
(A4-TB3). The Analog Inputs are NOT isolated and must be
referenced to the negative(-) dc bus.
Procedure
Procedure
1. De-energize and lock out all ac and dc voltages to ATevo.
2. Allow internal voltages to dissipate and verify with a voltmeter.
3. Remove safety shield.
4. Route remote analog inputs to the Auxiliary I/O Board (A4) through an unused enclosure
knockout.
5. Connect signal wiring (#22-14 AWG) to appropriate terminals (A4-TB3) of the Auxiliary I/O
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 5 May 2021
Page 131 of 171

Advertisement

Table of Contents
loading