HindlePower ATevo Series Operations page 20

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
3.5.2.
3.5.2. Floor-Mounting (Style-5054)
Floor-Mounting (Style-5054)
To install ATevo onto a horizontal surface, the standard enclosure does not need to be modified,
but a special floor mounting accessory is required. The kit includes a set of mounting brackets
that elevate the top of ATevo approximately 47in /1194mm above floor level, with provisions for
floor anchoring. The kit also includes appropriate hardware and installation instructions for the
floor-mounting procedure.
When floor-mounting ATevo, consider the following:
1. Locate anchor bolt holes at least 4.25in /108mm from any wall, to allow clearance behind
the mounting brackets.
2. Select conduit entrances with planned ac input and dc output wiring in mind. By using
pre-fab knockouts on enclosure sides or bottom, the enclosure shroud can be removed for
internal servicing without removing ATevo from the floor stand.
3. Location requirements:
a. Free of drips and splatter. If falling particles and liquids are a problem, install a
NEMA Type-2 drip shield accessory.
b. Between 0 and 122 °F / -18 and 50 °C, with relative humidity between 0% and 95%
non-condensing.
c. Must be free of flammable or explosive materials.
4. Maintain at least 6in /152mm of free air on all vented surfaces for cooling.
5. Allow 36in /914mm front clearance for operation and maintenance.
PROCEDURE
PROCEDURE
Install four (4) 0.25in / 6.4mm anchor bolts (not supplied) rated to support the unit weight plus
a minimum safety factor of two (2) times, into floor.
Assemble the floor-mounting accessory on to the anchor bolts as shown. Place ATevo onto
vertical posts, add appropriate mounting hardware, and tighten.
Refer to the following graphics for floor mounting patterns and enclosure footprints.
Floor-Mounting: Style-5054 Enclosure
Floor-Mounting: Style-5054 Enclosure
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 11 May 2021
Page 18 of 171

Advertisement

Table of Contents
loading

Table of Contents