HindlePower ATevo Series Operations page 143

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
Analog Input Scaling Assignment
Analog Input Scaling Assignment
ATevo can scale the analog input values such that the measurement can be represented in
primary units. To adjust the scaling, enter the primary value when the analog input is at 0
V, and the primary value when the analog input is 10.0 Vdc. ATevo will report the
measurements and adjust the alarm thresholds in true primary units.
To change the low scale value:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input (as shown above) >
'0V=:' > set desired digits
*
This number must represent the primary value when the input value is 0 V. If
no scaling is required, set 0.
To change the high scale value assigned to the analog input:
'10V=:' > set desired digits
*
This number must represent the primary value when the input value is 10.0
Vdc. If no scaling is required, set 10.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Page 141 of 171