HindlePower ATevo Series Operations page 119

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
output voltage is correct.
• If battery temperature falls below 32 °F / 0 °C, there will be no further increase in ATevo
output voltage. Likewise, if battery temperature rises above 122 °F / 50 °C, there will be
no further decrease in output voltage.
HOME
HOME Screen with TempCo Option
Screen with TempCo Option
Additional parameters appear on the HOME SCREEN when the TempCo option is installed and
enabled.
• The LARGE FONT voltage value is the actual charger output voltage, compensated for the
present battery temperature.
• Present battery temperature (in °C) appears in small font to the right of the actual
charger voltage.
• The charger set point voltage (at 25 °C) appears in small font directly below the present
battery temperature.
12.3.
12.3. Temperature Compensation
Temperature Compensation
Curves
Curves
The following graph depicts the dc voltage correction applied to ATevo output based on battery
temperature sensed by the TempCo probe (A10).
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en