HindlePower ATevo Series Operations page 39

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
PROCEDURE
PROCEDURE
1. Allow 30in / 762mm of wire inside enclosure, and trim excess.
2. Route annunciator wires to ATevo front panel door by following existing harness past door
hinge.
3. Use two (2) wire ties and allow a 4-6in / 102-153mm loop for the hinge.
4. Trim wires to length to connect to alarm terminal block (A1-TB6), and strip 0.25in / 6.4mm
of insulation.
5. Make connections at A1-TB6 and tighten compression screws.
NOTES
NOTES
1. Alarm contacts are rated at 0.5A / 125 Vac or Vdc.
2. Common Alarm relay terminal block (A1-TB6) is compression type, accepting wire sizes
#22-14 AWG.
3. Terminals are labeled in non-alarm condition.
4. If user alarm contacts (A1-TB6) are to drive inductive dc loads (e.g. a larger dc relay) an
external protective diode must be installed at the dc relay to avoid equipment damage.
Refer to
Application Note
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
JD5011-00.
Page 37 of 171