HindlePower ATevo Series Operations page 35

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
4.6.
4.6. Making DC Output Connections
Making DC Output Connections
Installer is responsible to provide suitable dc output, battery, and dc load wiring.
Guidelines for DC Connections
Guidelines for DC Connections
1. Size the dc wiring to minimize voltage drop. Acceptable wire size depends on the
installation. As a guideline, voltage drop should not exceed 1% of nominal output voltage
at full current. Refer to the following table to determine the voltage drops for various wire
sizes, currents and distances.
Voltage Drop per 100ft / 30.5m of Wire (for copper at 68 F / 20 C)
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
W W ir ire Sizing Chart
e Sizing Chart
Last modified: 11 May 2021
Page 33 of 171