Lamp Test & Display Of Firmware Versions - HindlePower ATevo Series Operations

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
TIMER.
To change the Equalize Method:
EQUALIZE METHOD > select other displayed option
When AUTOMATIC TIMER is selected, ATevo will:
• Automatically switch to EQUALIZE mode when power is restored after a loss of AC power
for greater than 12 seconds.
• Start EQUALIZE TIMER.
• Remain in EQUALIZE mode until either the EQUALIZE TIMER expires or the charge mode is
switched back to float mode manually.
When MANUAL TIMER is selected, ATevo will only switch to EQUALIZE MODE when the
mode is manually changed.
*
EQUALIZE METHOD button is in same relative location as EQLZ MTHD button on
legacy ATevo chargers. Functionality is equivalent in that when pressed, it
changes the equalize method. The Manual Equalize Method (no timer) available
in legacy ATevo chargers is not supported by ATevo.
7.1.4.
7.1.4. Lamp Test & Display of Firmware
Lamp Test & Display of Firmware
Versions
Versions
ATevo has a Lamp Test mode that is activated by pressing and holding the DOWN arrow button.
The Lamp Test will turn ON all front panel LEDs (except for the AC ON LED) and keep them on
until the DOWN arrow button is released. The AC ON LED will be lit during normal operating
conditions because it is driven by the power supply, and is not under software control.
When DOWN is released, ATevo will briefly display the charger's installed firmware versions,
then return to the HOME screen and resume normal operation.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en