EXAMPLE
EXAMPLE
Suppose you are dealing with a lead-acid battery whose temperature is 100 °F / 37.8 °C. As
shown on the graph, the dc output voltage should be approximately 97% of the 77 °F voltage.
If the float voltage is set on the front panel to 132 Vdc, the actual output voltage will be:
132 × 0.97 = 128 Vdc