Do NOT mount probe on: unpainted wood, bare galvanized metal, or plastic
surfaces. Consult battery manufacturer for mounting restrictions and adhesive
compatibilities.
5. To apply probe, clean mounting surface with isopropyl alcohol and dry thoroughly.
6. Remove protective backing from double-faced adhesive tape on probe, and press onto
surface.
7. Install supplied cable:
• Route end of cable that has two (2) stripped wires and a quick-connect terminal to the
inside of ATevo enclosure.
• Leave 30in / 762mm of cable inside enclosure. Run cable through a conduit that does not
contain power wiring.
• Route other end of cable to probe at the battery, and coil up excess cable.
• Make sure all wiring conforms to NEC, local, and site requirements
8. Attach interconnection cable to ATevo Power Board (A2-TB8) and EARTH terminal as shown
below:
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en