13.
13. Remote Sense
Remote Sense
ATevo regulates dc output voltage as measured at the charger's output connection (CB2+/-).
The Remote Voltage Sense feature permits ATevo to monitor and regulate the dc output voltage
at the battery. This feature is useful when long battery cables, causing resistive voltage-drop,
connect ATevo to the battery. All ATevo chargers can be wired to utilize this feature.
13.1.

13.1. Remote Sense Connection

Remote Sense Connection
Remote sensing:
• Compensates for voltage drop in dc wiring between ATevo and the battery.
• Directly monitors battery or dc bus voltage. The front panel meter displays actual voltage
at the battery or dc bus.
SCHEMATIC
SCHEMATIC
To wire ATevo for remote sensing, install twisted-pair cabling from the remote sense terminals
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
SECTION TOPICS
SECTION
TOPICS
Remote Sense Connection

Remote Sense Wiring Procedure

Configuring Remote Sense Jumpers

Disabling Remote Sense

Last modified: 2 March 2021