HindlePower ATevo Series Operations page 134

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
Board.
6. Strip each wire 0.25in / 6.4mm, and tighten terminal screws.
7. Replace the safety shield.
8. Re-energize ATevo.
Notes
Notes
• Analog Inputs are rated at 0-10Vdc.
• Terminal block is compression type and accepts #22-14 AWG.
• All Analog Inputs (AN1, AN2, AN3, AN4) must be referenced to the ATevo negative(-) bus
voltage (COM) terminal.
14.3.
14.3. Hardware Configuration
Hardware Configuration
The Auxiliary I/O Board (A4) requires two (2) hardware configurations:
• the Auxiliary I/O Board Address
• the Binary Input Voltage settings
Auxiliary I/O Board Address
Auxiliary I/O Board Address
The ATevo will support up to four (4) Auxiliary I/O Boards
(A4). Each Auxiliary I/O Board connected to ATevo must have
a unique address setting to identify it to the system. The
Auxiliary I/O dipswitch determines the Auxiliary I/O Board
Address.
The Auxiliary I/O dipswitch (A4-S1) contains three (3)
switches, and is located near the top center of the board.
Viewing the board with the"S1"silkscreen label to the left (as
shown), the switch UP position is ON, and the DOWN position
is OFF.
The Auxiliary I/O Board address is determined as follows:
• Auxiliary I/O Board #1: 1-ON, 2-ON, 3-ON
• Auxiliary I/O Board #2: 1-OFF, 2-ON, 3-ON
When supplied, ATevo is normally equipped with one (1) or two (2) Auxiliary I/O Boards.
However, for special units equipped with more:
• Auxiliary I/O Board #3: 1-ON, 2-OFF, 3-ON
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 5 May 2021
Page 132 of 171

Advertisement

Table of Contents
loading

Table of Contents