HindlePower ATevo Series Operations page 69

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
Configuring Ethernet Communications Adapter
Configuring Ethernet Communications Adapter
ATevo can support an optional Ethernet Adapter (A22) module.
The Ethernet Adapter module:
• can support SCADA protocols (DNP3 or Modbus)
• will support an ATevo web page interface (future)
• will permit a file transfer mechanism to upload/download files for firmware upgrade and
log file transfer (future)
Instructions on how to configure the Ethernet Adapter are found in the JA0102-54.
6.8.
6.8. Enabling/Disabling High Level
Enabling/Disabling High Level
Detect
Detect
ATevo has a dedicated hardware circuit that can shut down the charger should a catastrophic
microprocessor failure occur and the rectifier control become locked to the full 'on' state.
The setting for the Analog High Voltage Shutdown jumper determines whether the High Level
Detect circuit is enabled or disabled.
The High Voltage Shutdown jumper (J1) is located center right on the Main Control Board (A1).
To change the enable/disable status of the High Level Detect circuit:
1. Turn OFF (open) both AC Input (CB1) and DC Output (CB2) Circuit Breakers.
2. Open the ATevo front panel door.
3. Locate the Main Control Board (A1) on back of the door.
4. Locate jumper (J1) labeled 'High Level Detect Shutdown' on the center right of the Main
Control Board (A1).
5. Move jumper shorting block as follows:
a. 'EN' to enable the High Level Detect Shutdown
b. 'DIS' to disable the High Level Detect Shutdown
6. Close the front panel door.
7. Turn ON (close) both Circuit Breakers (CB1/CB2).
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 18 April 2022
Page 67 of 171