HindlePower ATevo Series Operations page 55

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
6.1.4.
6.1.4. Startup Procedure
Startup Procedure
After confirming that all connections to ATevo are properly made, start up as follows:
1. Turn ON (close) AC Input Circuit Breaker (CB1) first.
You should hear a soft hum from ATevo as output increases. Main ATevo Display should start
up and indicate dc output voltage. If the display does not light, do not proceed. Turn OFF
(open) the AC Breaker (CB1) and recheck connections.
!
If you attempt to turn ON the DC Output Circuit Breaker (CB2) first, it may trip
due to the filter capacitor in-rush.
2. Turn ON (close) the DC Output Circuit Breaker (CB2).
If any error codes or alarms appear on the Main ATevo Display and/or Alarm Indicator LEDs,
refer to
Section 8, Alarms & Indicators
indication before proceeding.
6.1.5.
6.1.5. HOME Screen
HOME Screen
The default HOME screen appears after power up showing the dc bus voltage and dc charger
current, along with the status for CHARGER MODE and EQUALIZE METHOD on the top line.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
to interpret the origin and resolution of the
Last modified: 12 February 2021