HindlePower ATevo Series Operations page 36

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
W W ir ire Size (
e Size (A A WG
10
10
8 8
6 6
4 4
2 2
0 0
Example
Example: 100ft / 30.5m of #8 AWG wire at 50A has a 3.1V drop.
2. ATevo is factory wired to regulate output voltage at the output terminals. If total voltage
drop is greater than 1% (e.g. 1.3V for a 130 Vdc system), remote sense wiring is
recommended (see
3. Do not run external ac and dc power wiring through the same conduit.
4. Facility-specific installation requirements take precedence.
Click the toggle below to see the DC Output connections required for your ATevo's enclosure
style:
I/O Connections (Style-5054)
I/O Connections (Style-5054)
1. Use a dc disconnect switch or circuit breaker between ATevo and the dc bus. This
device should have lockout capability to allow ATevo to be disconnected from the dc
bus for maintenance.
2. Remove safety shield per
3. Run dc wiring to Output Circuit Breaker (CB2).
4. Connect wires to appropriate locations on the DC Output Breaker (CB2+/-) as
indicated on drawing above.
5. Using a flat-blade screwdriver, securely tighten compression screws on DC Output
Breaker Terminals (CB2+/-).
6. Reinstall safety shield after you have made and checked all connections.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
WG) )
30
30
40
40
50
50
3.0V 4.0V 5.0V not recommended not recommended
1.9V 2.5V 3.1V not recommended not recommended
1.2V 1.6V 2.0V 3.0V
0.7V 1.0V 1.2V 1.9V
0.5V 0.6V 0.8V 1.2V
0.3V 0.4V 0.5V 0.7V
Section 13, Remote Sense
Removing Protective Safety Shield in Section
DC Curr r ent (Amper
DC Cur
ent (Amperes)
es)
75
75
100
100
not recommended
2.5V
1.6V
1.0V
).
4.
Page 34 of 171