HindlePower ATevo Series Operations page 68

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
6.6.
6.6. Disabling Alarms in Common Alarm
Disabling Alarms in Common Alarm
List
List
By default, the COMMON ALARM will activate when any ATevo alarm is active. If you disable an
alarm in the COMMON ALARM list the alarm will activate, but it will not cause the COMMON
ALARM to activate.
To disable an alarm in the COMMON ALARM list: MENU > COMMON ALARM > select alarm to
change status.
If an '[X]' appears to the left of the alarm, it will activate the COMMON ALARM. If '[ ]' appears,
it will not activate the COMMON ALARM.
6.7.
6.7. Configuring Communications
Configuring Communications
Adapters
Adapters
Configuring Serial Communications Adapters
Configuring Serial Communications Adapters
ATevo can support up to three (3) optional Serial Adapter modules.
Each Serial Adapter module can:
• support SCADA protocols (DNP3 or Modbus)
• be used as a standard communications interface to connect to external serial devices
• be used in various applications (such as Forced Load Sharing)
Instructions on how to configure Serial Communications Adapters are found in the JA0102-54.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 11 February 2021
Page 66 of 171