HindlePower ATevo Series Operations page 155

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
15.6.
15.6. Troubleshooting Forced Load
Troubleshooting Forced Load
Sharing ATevos
Sharing ATevos
• Ensure that at least one ATevo is configured as Primary on Port 2 or 3, and a Serial
Communication Adapter (A13) is plugged into that port.
• Ensure that at least one ATevo is configured as Secondary on Port 2 or 3, and a Serial
Communication Adapter (A13) is plugged into that port.
• Ensure that each Serial Communication Adapter board (A13x) used for Forced Load
Sharing is configured for RS-485, and is wired correctly.
• Verify that all ATevos are communicating. The Serial Communication Adapters (A13) have
a yellow and green LED that light briefly when the ATevo is sending or receiving data
respectively. These LEDs can be used to identify the problem source.
• Verify the voltage cabilbration of all ATevos connected in Forced Load Sharing.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 3 March 2021
Page 153 of 171