active until after the ATevo is RESET.
To configure ATevo Load Share Charger ID:
MENU > COMMUNICATION > Port 'X' setup > Charger ID > select (A, B, C, or D)
• Typically assign Primary charger as 'A' and Secondary chargers as 'B', 'C', and 'D'
• Example below shows Secondary charger that's assigned ID 'B'.
Press the EDIT/ENTER button to accept the new selection. Press the ESC button to return to the
previous screen. If a port setting was changes, the ATevo will prompt to RESET. Select YES to
RESET the ATevo. The new port settings will not become active until after the ATevo is RESET.
15.4.
15.4. Forced Load Sharing Operation
Forced Load Sharing Operation
The Primary ATevo runs a discovery poll each time it is reset or power-cycled. For discovery poll
to work, Secondary ATevo(s) need to be powered before the Primary.
During a discovery poll, the Primary ATevo queries ATevos with Charger IDs A, B, C, and D. The
Primary ATevo records the Charger ID of a responding ATevo in its database, and immediately
attempts to start sharing load with that ATevo. Once a Primary ATevo discovers a Secondary
ATevo, it expects it to be present the next time it is reset or power-cycled. As such, the Primary
will continuously poll any previously discovered Secondary whether it is present or not. It will
no longer matter which ATevo starts up first, following a power
cycle or reset.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Last modified: 3 March 2021
Page 149 of 171