HindlePower ATevo Series Operations page 66

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
6.5.
6.5. Configuring Relays
Configuring Relays
The Common Alarm Relay (or Main Board Relay) has three (3) configuration parameters that
allow the relay:
• to be assigned to a fault condition or status point
• to be assigned a delay period before activating the relay after the alarm or status
condition changes states
• to operate in a latching or non-latching mode
By default, the Main Board Relay is configured to indicate the status of the Common Alarm, but
this may be changed to indicate the status of any ATevo alarm or status state.
If this relay is configured to be 'latching', it will change to the active state after the configured
time delay, and remain in the active state even if the alarming condition is no longer present.
Latched relays must be cleared manually to ensure that they are acknowledged. See
9.6
for instructions on how to clear (or reset) latched relays.
Clicking on each toggle below will reveal a screenshot of how each relay setting is changed:
Common Alar
Common Alarm R
m Relay Configuration
elay Configuration
MENU > RELAYS > 'Relay Configuration'
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en