HindlePower ATevo Series Operations page 136

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
point has changed to active state and remains in active state for the configured time delay.
*
Software Configuration Naming: In the following subsections, Auxiliary I/O Board
relays are specified by "A4" board number (see Section 14.3), and relay number
on the associated board. For example: 'Aux 1 relay 3' specifies Relay #3 on
Auxiliary I/O Board #1.
To make changes to parameters for a relay on the Auxiliary I/O Board:
MENU > RELAYS > 'Relay Configuration' > select relay from options >
select parameter as in the toggles below:
R R elay Alar
elay Alarm Configuration
m Configuration
To change the alarm condition assigned to the relay:
MENU > RELAYS > 'Relay Configuration' > select relay from options
(as shown above) > 'Fault:' > select condition from list
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
Page 134 of 171