HindlePower ATevo Series Operations page 172

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
Firmware prior to v2.7.0 navigated directly to common alarm configuration. Firmware v2.7.0
now navigates to a menu that allows a user to select one of the three "aggregate" alarms to
configure. The lower right display shown is typical when "Common Alarm" has been selected.
"High Priority Alarm" and "Low Priority Alarm" displays are similar. Also new in v2.7.0 is that
alarms are listed in alphabetical order. In addition, alarm types that depend on optional
hardware are only displayed if the respective option is installed. Examples are "Battery
overtemp" and "Battery temp probe fail"; these are visible only if a battery temperature probe
is installed and enabled.
Disable Equalize
Disable Equalize
Disables the EQUALIZE output voltage mode which attempts to equalize the voltage among
battery cells. This action can be triggered by either a binary or analog input. An example use-
case for this feature would be when an aux input connected to a hydrogen sensor fires a 1%
Hydrogen Alarm, this input can disable the EQUALIZE charging.
This is presented as a new selection under the AUX INPUTS menu as an "Action" for either a
binary input
or an
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en
analog
input, as seen in the figure below.
Page 170 of 171