Overview
Overview
The Hindle Health System (HHS) is a powerful, user friendly, standard feature that tests and
reports on ATevo's operational health. Some portions of the HHS continuously run in the
background. Other parts require user intervention.
Components
Components
The Hindle Health System is composed of four (4) major components. The details of each are
shown by clicking on the toggles below:
Self
Self-Diagnotics Utility (runs in backgr
-Diagnotics Utility (runs in background)
ATevo microprocessors continuously run utilities that check hardware component operation
including: memory, communications interfaces, parameters, and discrete devices such as
relays.
They also test that all input values and measurements are within tolerance of reasonable
ranges. Some critical parameters such as dc voltage and dc current are sampled by multiple
processors and have redundant qualification requirements. Any errors detected are reported
immediately by alarms and/or status updates. The utilities provide possible causes and
proposed solutions to resolve issues found.
Hindle Health Button
Hindle Health Button
The Hindle Health Button is on the lower-right corner of the control panel overlay. When
pressed, it starts the user-assisted portion of the Hindle Health System. This process will check
areas of the battery charger that the continuous self-diagnostics cannot. For example, ATevo
cannot test a relay's performance without forcing it to change state. The user will be guided
through the test procedure via the Hindle Health Screens described later in this Section.
Hindle Health
Hindle Health LED
LEDs s
Hindle Health LED Indicators are at the bottom of the front panel overlay.
• GREEN LED , when lit, indicates ATevo is healthy.
• RED LED , when lit, indicates ATevo has an issue. Urgency of action required depends
upon if it is:
Blinking
Blinking
the microprocessor driving the display and front panel controls. LCD display may
be blank, frozen, or displaying corrupted data. Core microprocessor responsible
for charging the battery may still be operational.
Solid
Solid
LCD display will operate and be able to report the issue and give instructions on
how to resolve it. RED LED is illuminated when ATevo detects any error
condition, when any alarm is active, or when the Hindle Health System detects
Copyright HindlePower Inc. 2021
ound)
– Immediately replace Main Ctrl Board (A1). There is a critical failure of
– ATevo requires attention, but the condition is not critical. In most cases,