HindlePower ATevo Series Operations page 140

Float battery charger phase input–group ii (30-100 adc output)
Table of Contents

Advertisement

HindlePower Inc
Binary A
Binary Active State Assignment
ctive State Assignment
The Binary Active State assignment determines the normal and alarm state of the input.
To change the active state of a binary input on the Auxiliary I/O Board:
MENU > AUX INPUTS > 'Binary Input Configuration' > select input from options (as shown
above) > 'Active State' > select from 2 alarmed states
Binary Input Alar
Binary Input Alarm Enable
m Enable
The Binary Input Alarm Enable assignment determines whether the binary input will
generate an alarm, when it senses the alarmed state. Alarms generated by binary inputs
will appear by their configured name in the alarm list and on the bottom of the HOME
screen.
To enable or disable the Binary Input Alarm function:
MENU > AUX INPUTS > 'Binary Input Configuration' > select input from options (as shown
above) > 'Alarm:' > select from 2 alarmed states
Binary Input A
Binary Input Action Assignment
ction Assignment
The Binary Input Action assignment links the binary input to a changer control. Examples of
a charger control include rectifier remote shutdown, or float/equalize mode control. ATevo
will execute assigned charger control when the binary input is in the active state.
Copyright HindlePower Inc. 2021
ATevo Operations–Single Phase Input–Group II (30-100 Adc Output) - 1_en