70
Mounting
6.2.2
WAGO DIN Rails
WAGO carrier rails meet the electrical and mechanical requirements shown in the
table below.
Table 42: WAGO DIN Rails
Item No.
210-112
210-113
210-197
210-114
210-118
210-198
210-196
Observe the mounting distance of the DIN rail when the load is increased!
With increased vibration and shock load, mount the DIN rail at a mounting
distance of max. 60 mm.
6.3
Spacing
A minimum distance of at least 35 mm to cable ducts and housing/frame
walls must be maintained for the entire fieldbus node.
For components that are adjacent on the DIN-rail, this distance can fall
below this minimum if necessary.
Figure 8: Spacing
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
Description
35 × 7.5; 1 mm; steel; bluish, tinned, chromed; slotted
35 × 7.5; 1 mm; steel; bluish, tinned, chromed; unslotted
35 × 15; 1.5 mm; steel; bluish, tinned, chromed; slotted
35 × 15; 1.5 mm; steel; bluish, tinned, chromed; unslotted
35 × 15; 2.3 mm; steel; bluish, tinned, chromed; unslotted
35 × 15; 2.3 mm; copper; unslotted
35 × 8.2; 1.6 mm; aluminum; unslotted
WAGO I/O System Compact