110 e!RUNTIME Runtime Environment
9.4.3

Analog Temperature Inputs

The analog temperature sensor inputs PT1+ / PT1– and PT2+ / PT2– are
represented at a resolution of 1 digit per 0.1 °C via the INT data type (16 bit).
Table 51: Process Image – Analog Temperature Inputs
Chan-
nel
PT1+ /
PT1–
PT2+ /
PT2–
*Temperature values below 0 °C are represented in two's complement binary and
hexadecimal.
9.4.4

Digital Inputs

The digital inputs DI1 ... DI8 are represented per channel via the BOOL data
type. In addition, the digital inputs are represented via the BYTE data type.
Table 52: Process Image – Digital Inputs
Chan-
nel
...
DI [1
8]
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
9.4.5

Digital Outputs

The digital outputs DO1 ... DO4 are represented per channel via the BOOL data
type. In addition, the digital outputs are represented via the BYTE data type.
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
Pin
Data
Mea-
Type
sured
Value
–60 °C
X13.1 /
...
X13.2
350 °C
INT
X13.3 /
>
X13.4
350 °C
Pin
Data
Mea-
Type
sured
Value
X12
BYTE
X12.3
X12.4
X12.5
0 /
+24 V
X12.6
DC
BOOL
X12.7
X12.8
X12.9
X12.10
WAGO I/O System Compact
751-9301 Compact Controller 100
Value Range
Hex.
Dec.
...
0xFDA8*
...
–600
0x0DAC
0x0DAC
3500
Value Range
Hex.
Dec.
...
...
0x00
0xFF
0
Bin.
1111.1101.
...
1010.1000*
3500
0000.1101.
1010.1100
0000.1101.
1010.1100
Bin.
...
0000.0000
255
1111.1111
TRUE /
FALSE