Network Connection Led; Lnk Act" Led; Table 56: "Lnk Act" Led Diagnostics - WAGO Compact Controller 100 Manual

Table of Contents

Advertisement

WAGO I/O System Compact
751-9301 Compact Controller 100
Table 55: RUN LED Diagnostics
Status
Red,
goes out longer
Red, flashing
Orange/green
flashing
Orange
OFF
10.1.2

Network Connection LED

10.1.2.1

"LNK ACT" LED

The "LNK ACT" LED indicates following diagnostics:

Table 56: "LNK ACT" LED Diagnostics

Status
Off
Green
Green flashing
Explanation
Cold start reset
completed
At least one
application after in the
"STOP" status after
exception (e.g.,
memory access error)
Load above threshold
value 1
Runtime system in
debug state
(breakpoint, single
step, individual cycle)
No runtime system
loaded
Explanation
No network
communication via
port
Connection to the
physical network
available
Network
communication via
port
Version 1.1.0, valid from FW Version 03.08.07(20)
Remedy
---
Start the application with a reset via the
mode selector switch or in the connected
IDE.
If the application cannot be started,
restart the controller.
Contact WAGO Support if the error
occurs again.
Try to reduce the load on the system:
-
Change the CODESYS program.
-
End any fieldbus communication that
is not essential, or reconfigure the
fieldbuses.
-
Remove any non-critical tasks from
the RT area.
-
Select a longer cycle time for IEC
tasks.
Resume the application in the connected
IDE with single step or start.
Remove the breakpoint if necessary.
If the connection has been interrupted,
set the mode selector switch to "STOP"
and then back to "RUN" to enable the
application to continue
Enable a runtime system, e.g., via the
WBM.
Remedy
Check network connections and network
settings.
---
Diagnostics 113