Analog Outputs; Communication Interface; Table 10: Analog Outputs - "X6; Table 11: Communication Interface Rs-485 - "X11 - WAGO Compact Controller 100 Manual

Table of Contents

Advertisement

30
Properties

4.1.3.5.2 Analog outputs

The controller generates signals with standardized values of 0 ...+10 V for the
field range.
The product has 2 output channels, making two 2-wire actuators possible.
The actuators are connected via the AO1 and ground connections or AO2 and
ground.
The channels have a common ground potential.
The output signal is output at a resolution of 12 bits.
The internal power supply powers the module.
Table 10: Analog outputs – "X6"
Contact
1
2
3
4
4.1.3.6

Communication Interface

The communication interface integrated in the controller allows devices with an
RS-485 interface to be connected.
The D +, D-, GNDRS and SHRS connections are used for wiring to the
communication partner.
The shield connection directly connects to the DIN-rail.
The interface operates in accordance with DIN 66259.
The connected device can communicate directly via the controller used. The
active communication channel works independently of the higher-level bus
system in half-duplex mode at up to 115200 baud.
The RS-485 interface guarantees a high level of interference immunity through
differential transmission and electrically isolated signals.
Table 11: Communication Interface RS-485 – "X11"
Contact
1
2
3
4
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
Signal
AO1
GND
AO2
GND
Signal
Description
D+
Transmit/receive data +
D–
Transmit/receive data –
GND
Ground
RS
SH
Supply voltage
RS
WAGO I/O System Compact
751-9301 Compact Controller 100
Description
Analog output 1
Ground
Analog output 2
Ground

Advertisement

Table of Contents
loading

This manual is also suitable for:

751-9301

Table of Contents