Plc Runtime Services" Page; Table 94: Wbm "Plc Runtime Services" Page - "General Configuration" Group; Table 95: Wbm "Plc Runtime Services" Page - "Codesys V2" Group - WAGO Compact Controller 100 Manual

Table of Contents

Advertisement

WAGO I/O System Compact
751-9301 Compact Controller 100

15.1.1.2.15 "PLC Runtime Services" Page

The settings for various services of the enabled runtime system are displayed on
the "PLC Runtime Services" page.
"General Configuration" Group
Table 94: WBM "PLC Runtime Services" Page – "General Configuration" Group
Parameter
Port Authentication
Password
Confirm Password
Click the [Set Password] button to apply the change. The change takes effect
immediately.
"CODESYS V2" Group
This group only appears if the controller supports the CODESYS V2 runtime
system.
Table 95: WBM "PLC Runtime Services" Page – "CODESYS V2" Group
Parameter
CODESYS 2 State
Webserver enabled
Communication enabled
Communication Port
Number
Port authentication enabled
Click the [Submit] button to apply the change.
The change in authentication takes effect after the next restart.
All other changes take effect immediately.
Explanation
Specify the new password for port authentication.
Enter the new password again for confirmation.
Explanation
This displays the status (enabled/disabled) of the
CODESYS V2 runtime system.
Enable or disable the CODESYS V2 Webserver for
the CODESYS web visualization.
Enable or disable the communication between the
CODESYS V2 runtime system and the
CODESYS V2 programming system.
Enter here the port number for communication with
the CODESYS V2 programming system. The default
value is 2455.
Define here whether port authentication is enabled.
If this is enabled, the password specified under
"General Configuration" must be entered when
logging in via CODESYS V2 IDE.
Version 1.1.0, valid from FW Version 03.08.07(20)
Appendix 161
Manual