Climatic Environmental Conditions; Table 30: Technical Data - Climatic Environmental Conditions - WAGO Compact Controller 100 Manual

Table of Contents

Advertisement

WAGO I/O System Compact
751-9301 Compact Controller 100
4.3.13

Climatic Environmental Conditions

Table 30: Technical Data – Climatic Environmental Conditions
Surrounding air temperature (operation) −25 ... +60 °C
Surrounding air temperature (storage)
Relative humidity (without
condensation)
Operating altitude above sea level
Pollution degree
Overvoltage category
Protection type
Special conditions
The permissible ambient temperatures in relation to the installation positions can
be found in section "Mounting" > "Installation Position".
−25 ... +85 °C
5 ... 95 %
2000 m
2
II
IP20
Ensure that additional measures for
components are taken, which are
used in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
The permissible temperature range
of the connecting cable must be
dimensioned based on the
mounting position and current
intensity, as the temperature of the
terminal connection can be up to
25 °K above the maximum
expected surrounding air
temperature (at 10 A).
Version 1.1.0, valid from FW Version 03.08.07(20)