40
Properties
4.3.10

Digital outputs

Table 27: Technical Data – Digital Outputs
Number of digital outputs
Output voltage
Load types
Reverse voltage protection
Switching frequency (max.)
Output current max., 1 output
4.3.11

Analog inputs

Table 28: Technical Data – Analog Inputs
Number of analog inputs
Connection types
Input voltage, measurement range
Input voltage (max.)
Typ. input resistance
Resolution
Temperature coefficient
4.3.12

Analog outputs

Table 29: Technical Data – Analog Outputs
Number of analog outputs
Output voltage, measurement range
Load impedance
Typ. settling time
Resolution
Measurement error at 25 °C
Temperature coefficient
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
WAGO I/O System Compact
751-9301 Compact Controller 100
4
24 VDC
DC, general use (according to UL
61010-2-201, paragraph 4.4.2.101)
Yes
1 kHz
0.5 A, short-circuit protected
2
Single-ended
0 ... 10 V
±30 V
> 100 kΩ
16 bits
< ±0.01 % / K of full scale value
2
0 ... 10 V
> 5 kΩ
100 ms
12 bit
< ±0.2 % of full scale value
< ±0.005 % / K of full scale value