36
Mounting
5.3.2
WAGO DIN Rail
WAGO carrier rails meet the electrical and mechanical requirements shown in the
table below.
Table 16: WAGO DIN Rail
Order number
210-112 /-113
210-197 /-114
210-118
210-198
210-196
For vibration loads > 4g, observe the following installation instructions:
•
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
•
Make the open conductor length between strain relief and wire connection
as short as possible.
•
Use the reinforced end stop 249-197.
•
When using the PFC200 750-8202/040-00x, carrier rails without an oblong
hole must also be used. Alternatively, a material thickness of min. 1.5 mm
must be maintained.
•
When using the PFC200 750-8206/040-00x or 750-821x/040-010, carrier
rails without an oblong hole with a material thickness of min. 2.3 mm must
also be used.
Table 17: Permissible WAGO Carrier Rails When Using XTR PFC200 for Vibration Loads >4g
Item
Number
210-113
210-114
210-197
210-118
Manual
Version 1.3.0
Description
35 × 7.5;
1 mm; steel blue chromated; slotted/unslotted
35 × 15; 1.5 mm; steel blue chromated; slotted/unslotted
35 × 15; 2.3 mm; steel blue chromated; unslotted
35 × 15; 2.3 mm; copper; unslotted
35 × 8.2; 1.6 mm; aluminum; unslotted
750-8202/040-00x
×
×
×
×
WAGO I/O System 750 XTR
750-xxxx/040-xxx System Manual XTR
750-8206/040-00x
–
–
–
×
750-821x/040-010
–
–
–
×