144 Appendix
"Custom Routes" Group
Each configured static route has its own area in the display. If no static routes
have been entered, "(no custom routes)" is displayed.
Table 74: WBM "Routing" Page – "Custom Routes" Group
Parameter
Enabled
Destination Address
Destination Mask
Gateway Address
Gateway Metric
Interface
Click the [Submit] button to apply the changes. The changes take effect
immediately.
To add a new route, click the [Add] button. The change takes effect immediately.
Click the [Delete] button to delete an existing route. The change takes effect
immediately.
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
751-9301 Compact Controller 100
Explanation
Specify whether the selected route should be used.
Disabled
The route is not used.
Enabled
The route is used.
Specify whether any network devices or only a
specific network device or device pool should be
accessible.
Any network devices can be
Default
reached.
Only a specific network device
Network address
or device from the specified
address pool can be reached.
Enter the subnet mask of the device.
If "default" is entered for Destination Address, the
value "0.0.0.0" must be entered.
Enter the address of the gateway.
If the "Interface" input field is empty, an entry is
required here. If a value is entered in the "Interface"
input field, the input here is optional.
Set the number used as the metric.
When there are multiple routes with the same
destination address and destination mask, the
metric specifies the gateway to which network data
packets are first sent. Priority is given to routes with
a lower value for the metric.
The lowest value is 0.
The highest value is 2³² - 1 = 4294967295.
Enter an interface via which the packets sent to the
destination address are routed. Bridges (br0-br3) as
well as modems (wwan0) or VPN interface names
can be used.
If the "Gateway Address" input field is empty, an
entry is required here. If a value is entered in the
"Gateway Address" input field, the input here is
optional.