Removing an RPS-150XT Redundant Power Supply
6. Carefully slide the power supply all the way into the power supply bay.
Figure 284: Installing an ExtremeSwitching 2000 W AC Power Supply
7. Push the power supply in until the latch snaps into place.
8. Connect the power cord to the power supply and to a grounded AC power outlet.
9. If the power supply is equipped with a power cord retainer, use the retainer to secure the power cord
to the power supply.
Removing an RPS-150XT Redundant Power Supply
To remove an installed RPS-150XT that is attached to a switch, follow these steps.
Caution
Observe all ESD precautions when handling sensitive electronic equipment.
Note
The switch should not be powered on during installation or removal of the power supply. This
is not a hot-swap procedure. Follow the steps in the order specified.
1. Unplug the AC power cord from the AC power source first and then from the power supply.
2. Disconnect the RPS cable from the Redundant Power Supply connector at the rear of the power
supply.
3. Disconnect the RPS cable from the Redundant Power Supply connector on the switch.
4. If the power supply is installed in a rack, remove it from the rack:
a. Holding the power supply securely, remove the captive screws that secure it to the STK-
RPS-1005CH3 shelf.
342 ExtremeSwitching Hardware Installation Guide
Caution
Do not slam the power supply into the switch.
Warning
Always be sure that the source outlet is properly grounded before plugging the AC power
cord into the AC power supply.
Replacing AC Power Supplies
Need help?
Do you have a question about the ExtremeSwitching X435 Series and is the answer not in the manual?
Questions and answers