Parameters
List of parameters
p10007
BI: SI input terminal forced checking procedure F-DO 0 ... 3 / SI DI fcp F-DO
TM54F_MA
Can be changed: C2
Data type: Unsigned32 / Binary
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Selects an input terminal (input terminal of the Control Unit or a Terminal Module) to start the test stop.
The test stop is started with a 0/1 signal at the input terminal and is then only possible if the TM54F is not in the
commissioning mode (p0010 = 0).
Dependency:
Refer to: p10001, p10003, p10041, p10046
Notice:
It is not permissible to use an input on the TM54F to start the test stop.
p10008
SI operating mode TM54F / SI op_mode TM54F
TM54F_MA,
Can be changed: C2
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the operating mode for the Terminal Module 54F (TM54F).
Values:
0:
1:
Note:
Parameter is being prepared - for this firmware version, the function interface is not supported.
p10010[0...5]
SI drive object assignment / SI drv_obj assign
TM54F_MA,
Can be changed: C2
TM54F_SL
Data type: Unsigned16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the drive object number for the drives that are available.
Index:
[0] = Drive 1
[1] = Drive 2
[2] = Drive 3
[3] = Drive 4
[4] = Drive 5
[5] = Drive 6
Notice:
If, for a drive, safety with TM54F is activated (p9601 = 5), then its drive object number must be precisely entered
into one index of p10010.
p10011[0...5]
SI drive group assignment / SI drv_gr assign
TM54F_MA,
Can be changed: C2
TM54F_SL
Data type: Unsigned16
P-Group: Safety Integrated
Not for motor type: -
Min
1
Description:
Sets the drive group for the drives that are available.
A drive group is a combination of several drives with the same types of behavior.
1-1050
Function interface
Control interface
Calculated: -
Dynamic index: -
Units group: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Max
1
Calculated: -
Dynamic index: -
Units group: -
Max
32
Calculated: -
Dynamic index: -
Units group: -
Max
4
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Access level: 3
Func. diagram: 2848
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2846, 2848
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2848
Unit selection: -
Expert list: 1
Factory setting
1