F01612
SI CU: STO inputs for power units connected in parallel different
Drive object:
SERVO, VECTOR
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-based "Safety Integrated" function on the Control Unit (CU) has identified different states of the AND'ed
STO inputs for power units connected in parallel and has initiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9658), fault F01600 (SI CU: STOP A initiated)
is output.
Fault value (r0949, interpret binary):
Binary image of the digital inputs of the Control Unit that are used as signal source for the function "Safe Torque Off".
Remedy:
- check the tolerance time SGE changeover and if required, increase the value (p9650).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
Note:
CU: Control Unit
F-DI: Failsafe Digital Input / SGE: Safety-relevant input
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
N01620 (F, A)
SI CU: Safe Torque Off active
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Torque Off" (STO) function has been selected on the Control Unit (CU) using the input terminal and is
active.
Note:
This message does not result in a safety stop response.
Remedy:
None necessary.
Note:
CU: Control Unit
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
Reaction upon F:
OFF2
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
N01621 (F, A)
SI CU: Safe Stop 1 active
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Stop 1" (SS1) function has been selected on the Control Unit (CU) and is active.
Note:
This message does not result in a safety stop response.
Remedy:
None necessary.
Note:
CU: Control Unit
SI: Safety Integrated
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
Reaction upon F:
OFF3
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Faults and Alarms
List of faults and alarms
3-1475