Siemens SINAMICS S Series List Manual page 1471

Hide thumbs Also See for SINAMICS S Series:
Table of Contents

Advertisement

Remedy:
Again set the required standard telegram (p0922).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A01507 (F, N)
BICO: Interconnections to inactive objects present
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
There are BICO interconnections as signal drain from a drive object that is either inactive/not operational.
The BI/CI parameters involved are listed in r9498.
The associated BO/CO parameters are listed in r9499.
The list of the BICO interconnections to other drive objects is displayed in r9491 and r9492 of the de-activated drive
object.
Note:
r9498 and r9499 are only written into, if p9495 is not set to 0.
Alarm value (r2124, interpret decimal):
Number of BICO interconnections found to inactive drive objects.
Remedy:
- set all open BICO interconnections centrally to the factory setting with p9495 = 2.
- make the non-operational drive object active/operational again (re-insert or activate components).
Reaction upon F:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (ENCODER, IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (ENCODER, IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A01508
BICO: Interconnections to inactive objects exceeded
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum number of BICO interconnections (signal drains) when de-activating a drive object was exceeded.
When de-activating a drive object, all BICO interconnections (signal drains) are listed in the following parameters:
- r9498[0...29]: List of the BI/CI parameters involved.
- r9499[0...29]: List of the associated BO/CO parameters.
Remedy:
The alarm automatically disappears as soon as no BICO interconnection (value = 0) is entered in r9498[29] and
r9499[29].
Notice:
When re-activating the drive object, all BICO interconnections should be checked and if required, re-established.
F01510
BICO: Signal source is not float type
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The selected connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, interpret decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Faults and Alarms
List of faults and alarms
3-1471

Advertisement

Table of Contents
loading

Table of Contents