Parameters
List of parameters
p10046
SI test sensor feedback signal input DI 20 ... 23 / SI test sens FS
TM54F_MA,
Can be changed: C2
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Sets the test of the feedback line for forced checking procedure.
Bit field:
Bit
Signal name
00
Read back F-DO 0 in DI 20
01
Read back F-DO 1 in DI 21
02
Read back F-DO 2 in DI 22
03
Read back F-DO 3 in DI 23
Note:
F-DO: Failsafe Digital Output
r10051.0...9
CO/BO: SI digital inputs status / SI DI status
TM54F_MA,
Can be changed: -
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the single-channel status of the safety digital inputs F-DI 0 .. 9 at Terminal Module 54F (TM54F).
If a safety function is assigned to an input (e.g. via p10022), then the following applies:
- logical "0": The safety function is selected
- logical "1": The safety function is canceled
The interrelationship between the logical level and the external voltage level at the input depends on the parameter-
ization (refer to p10040) of the input as either NC or NO contact and is aligned to the use of a safety function:
With 24 V at the input, NC contacts have a logical "1" level, for 0 V at the input, a logical "0" level.
This means that an NC/NC contact parameterization of 0 V at both inputs of the F-DI selects the safety function, for
24 V at both inputs, deselects the safety function.
With 24 V at the input, NO contacts have a logical "0" level, for 0 V at the input, a logical "1" level.
This means that for an NC/NO contact parameterization, the level 0 V/24 V selects the safety function, the level 24
V/0 V deselects the safety function.
Bit field:
Bit
Signal name
00
F-DI 0
01
F-DI 1
02
F-DI 2
03
F-DI 3
04
F-DI 4
05
F-DI 5
06
F-DI 6
07
F-DI 7
08
F-DI 8
09
F-DI 9
Note:
F-DI: Failsafe Digital Input
1-1064
Calculated: -
Dynamic index: -
Units group: -
Max
-
1 signal
Test active
Test active
Test active
Test active
Calculated: -
Dynamic index: -
Units group: -
Max
-
1 signal
Logical 1
Logical 1
Logical 1
Logical 1
Logical 1
Logical 1
Logical 1
Logical 1
Logical 1
Logical 1
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Access level: 3
Func. diagram: 2848
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
FP
No test
-
No test
-
No test
-
No test
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
FP
Logical 0
2850
Logical 0
2850
Logical 0
2850
Logical 0
2850
Logical 0
2850
Logical 0
2851
Logical 0
2851
Logical 0
2851
Logical 0
2851
Logical 0
2851