Remedy:
- read-out diagnostics parameter (r9999).
- contact the Hotline.
See also: r9999 (Software error internal supplementary diagnostics)
Reaction upon F:
OFF2
Acknowl. upon F:
POWER ON
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01005
Firmware download for DRIVE-CLiQ component unsuccessful
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Firmware was not able to be downloaded into a DRIVE-CLiQ component.
Fault value (r0949, interpret hexadecimal):
xxyyyy hex: xx = component number, yyyy = cause of the fault
yyyy = 000B hex = 11 dec:
DRIVE-CLiQ component has detected a checksum error.
yyyy = 000F hex = 15 dec:
The selected DRIVE-CLiQ component did not accept the contents of the firmware file.
yyyy = 0012 hex = 18 dec:
Firmware version is too old and is not accepted by the component.
yyyy = 0013 hex = 19 dec:
Firmware version is not suitable for the hardware release of the component.
yyyy = 0065 hex = 101 dec:
After several communication attempts, not response from the DRIVE-CLiQ component.
yyyy = 008B hex = 139 dec:
Initially, a new boot loader is loaded (must be repeated after POWER ON).
yyyy = 008C hex = 140 dec:
Firmware file for the DRIVE-CLiQ component not available on the CompactFlash card.
yyyy = 008F hex = 142 dec:
Component has not changed into the mode for firmware download.
yyyy = 009C hex = 156 dec:
Component with the specified component number is not available (p7828).
yyyy = Additional values:
Only for internal Siemens troubleshooting.
Remedy:
- check the selected component number (p7828).
- check the DRIVE-CLiQ connection.
- save suitable firmware file for download in the directory /siemens/sinamics/code/sac/.
- after POWER ON has been carried out again for the DRIVE-CLiQ component, download the firmware again.
A01006
Firmware update for DRIVE-CLiQ component required
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The firmware of a DRIVE-CLiQ component must be updated as there is no suitable firmware or firmware version in
the component for operation with the Control Unit.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Firmware update using the commissioning software:
The firmware version of all of the components on the "Version overview" page can be read in the Project Navigator
under "Configuration" of the associated drive unit and an appropriate firmware update can be carried out.
Firmware update via parameter:
- take the component number from the alarm value and enter into p7828.
- start the firmware download with p7829 = 1.
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Faults and Alarms
List of faults and alarms
3-1435