Siemens SINAMICS S Series List Manual page 1444

Hide thumbs Also See for SINAMICS S Series:
Table of Contents

Advertisement

Faults and Alarms
List of faults and alarms
Remedy:
- use the current version of the commissioning software.
- modify the offline project and carry out a new download (e.g. compare the number of drive objects, motor, encoder,
power unit in the offline project and at the drive).
- change the drive system (is a drive rotating or is there a message/signal?).
- carefully note any other messages/signals and remove their cause.
F01044
CU CompactFlash: Message incorrectly written
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error was detected when loading the message descriptions (FDxxxyyy.ACX) saved on the CompactFlash card.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Replace the CompactFlash card.
A01045
CU CompactFlash: Configuring data invalid
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An invalid data type was detected when evaluating parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX
or CCxxxyyy.ACX, saved on the CompactFlash card.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit. Operation without any restric-
tions is then possible.
After downloading the project, save the parameterization in STARTER using the function "Copy RAM to ROM" or
with p0977 = 1. This means that the incorrect parameter files are overwritten on the CompactFlash card.
A01046 (F)
CU CompactFlash: Configuring data invalid
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An invalid data type was detected when evaluating the parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxx-
yyy.ACX or CCxxxyyy.ACX saved on the CompactFlash card.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit. Operation without any restric-
tions is then possible.
After downloading the project, save the parameterization in STARTER using the function "Copy RAM to ROM" or
with p0977 = 1, so that the incorrect parameter files are overwritten on the CompactFlash card.
Reaction upon F:
A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A01047 (F)
ACX: Write to parameter error
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the parameters files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX or CCxxxyyy.ACX, saved on
the CompactFlash card, a parameter value was not able to be transferred into the Control Unit memory.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit. Operation without any restric-
tions is then possible.
After downloading the project, save the parameterization in STARTER using the function "Copy RAM to ROM" or
with p0977 = 1. This means that the incorrect parameter files are overwritten on the CompactFlash card.
3-1444
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007