X523.1
AI 0
X523.2
<2>
-11...+11 V
p4066 [0]
0
1
<1> When interconnected, the output signals are referred to the reference quantities p200x or p205x (100%
<2> Differential inputs!
For input signals referred to ground, terminal 2 or 4 must be connected to reference potential M.
<3> Caution:
The voltage between an input and ground must not exceed 35 V.
The voltage between the inputs must not exceed 35 V.
<4> If the PROFIdrive communication is operated with clock cycle synchronism (r2064[0] = 1), the time slice automatically adjusts to the PROFIdrive
clock cycle (r2064[1]). When the PROFIdrive interface is in this mode, p4099 does not influence the time slice for TM41.
1
2
DO: TM41
Terminal Module 41 (TM41) - Analog input (AI 0)
Offset
Hardware smoothing
-20.000...20.000
p4063[0] (0.000)
100 µs
A
+
+
D
Simulation mode
-20.000...20.000
p4098[0] (0.000)
p4067 [0]
Smoothing
(0)
0.0...1 000.0 ms
p4053[0] (0.0)
0
x
-1
1
3
4
<3>
[V]
p4097[0]
r4052[0]
-1000.00...1000.00 %
p4060[0] (100.00)
0
1
-1000.00...1000.00 %
p4058[0] (0.00)
Enable
Window to suppress noise
p4069 [0]
0.00...20.00 %
(1)
p4068[0] (0.00)
0
0 %
y = x if
y
|y - x| > p4068
1
otherwise y = y(old)
p20xx).
5
6
fp_9663_51_eng.vsd
07.12.06 V02.05.00
p4099[1] (4000.00 µs)
<4>
-11.000...11.000
-11.000...11.000
p4057[0] (0.000)
p4059[0] (10.000)
y
[%]
y
2
[%]
x
y
x
x
x
2
1
[V]
y
1
scaling
x
Reference quantities
1
y
x
p200x
x
2
x
x
1
2
100%
r4055[0]
<1>
7
8
Function diagram
- 9663 -